OVAL BC2000 Communication Driver is the driver to communicate with Batch Controller of OVAL in Japan.
<Figure 1> is read setting example of OVAL BC2000 communication driver.
![]() |
<Figure 1> Read setting example of OVAL BC2000 communication driver |
Device part of <Figure 1> input Com Port(COM1), Baud Rate(9600), Parity Bit(0), Data Bit(8), Stop Bit(1) respectively, according to setting of controller.
Also, you can set 'wait time after ID selection'( 0 ~ 2000 m Sec, default = 50 ) by using option part.
OVAL BC2000 communication driver¡¯s read schedule
Read schedule setting parameters are as follows:
1) Station – Controller station number = 0 ~ 99.
2) Read Command – Command = BS, T?, R?,C?,O? ( Refer to <Table 1> )
3)Read Start Address– Don't care.
4)Save start address for Communication Server – Saving start address of Communication Server.
5) Read Size – fixed to 1.
Read schedule example)
READ, 99, BS, 0, 0, 1,
FLOAT, 99, T?, 0, 5, 1,
FLOAT, 99, R?, 0, 10, 1,
<Table 1> is read command and contents of OVAL BC2000 communication driver.
Read Command |
Contents |
BS |
Status |
T? |
Total (batch/netTotal/grossTotal) |
R? |
Rate |
C? |
Temperature |
O? |
Total and Rate (batch/Rate/netTotal/grossTotal) |
<Table 1> read command and contents of OVAL BC2000 communication driver |
OVAL BC2000 communication driver store the same data in WORD, DWORD, FLOAT memory, but the data format are different.
If you click the icon
in protocol option part, you
can see the dialogue box such as <Figure 2>. you can also set read schedule by
using this part.
![]() |
<Figure 2> Example of OVAL BC2000 communication driver¡¯s Option dialogue box |
You can set read schedule by using
,
,
button and listbox of <Figure
2>.
Wait time after ID selection( 0 ~ 2000 m Sec, default = 50 ) can set by using the part of ¡®Wait Time After ID Selection¡¯ shown in <Figure 2>
When you click Add button or Edit button in dialogue box of <Figure 2>, dialogue box of <Figure 3> is shown.
![]() |
<Figure 3> Example of OVAL BC2000 communication driver¡¯s read schedule Add/Edit dialogue box |
You can write the setting value by using write settings.
Digital Write
Digital write setting parameters are as follows:
1) PORT Port no. (0 ~ 255)
2) STATION Controller station number = 0 ~ 99.
3) ADDRESS Saving start address of Communication Server (Decimal address)
4) Extra1 Write command BH, BR, BC ( Refer to <Table 2> )
BH : stop, value = Don't care.
BR : reset, value = Don't care.
BC : start, value = Don't care.
5) Extra2 Don't care.
Write example 1)
PORT : 12 , STATION : 99, ADDRESS : 0000, EXTRA1 : BH, EXTRA2 :
The setting parameter shown above is an example of stop the OVAL BC2000 device (ID 99) connected to port 12.
Write example 2)
PORT : 12 , STATION : 99, ADDRESS : 0000, EXTRA1 : BR, EXTRA2 :
The setting parameter shown above is an example of reset the OVAL BC2000 device (ID 99) connected to port 12.
Write example 3)
PORT : 12 , STATION : 99, ADDRESS : 0000, EXTRA1 : BC, EXTRA2 :
The setting parameter shown above is an example of start the OVAL BC2000 device (ID 99) connected to port 12.
Analog Write
Analog write setting parameters are as follows:
1) PORT Port no. (0 ~ 255)
2) STATION Controller station number = 0 ~ 99.
3) ADDRESS Saving start address of Communication Server (Decimal address)
4) Extra1 Write command BV,BH,BR,BC ( Refer to <Table 2> )
BV : setting batch value, value = Enter up to 8 digits including integers and decimal places. (Decimal places is discarded, eg 0.12345 ¡æ 0.12 for 2 decimal places).
BH : stop, value = Don't care.
BR : reset, value = Don't care.
BC : start, value = Don't care.
5) Extra2 Don't care.
6) Value Batch value
Write example 1)
PORT : 12 , STATION : 99, ADDRESS : 0000, EXTRA1 : BC, EXTRA2 : , VALUE : 11.1
The setting parameter shown above is an example of Set the batch value of the OVAL BC2000 device (ID 99) connected to port 12 to 11.1.
<Table 2> is write command and contents of OVAL BC2000 communication driver.
write Command |
Contents |
BV |
Batch |
BH |
Stop |
BR |
Reset |
BC |
Start |
<Table 2> Write command and contents of OVAL BC2000 communication driver |
Connection of main power line and communication cable are as follows.
<Figure 4>is Connection example of main power line(red) and communication cable(blue) to OVAL BC2000 Series
![]() |
<Figure 4> Connection example of main power line(red) and communication cable(blue) to OVAL BC2000 Series |
Connection of main power line
Connect 220 V AC to the power input of <Figure 4> (only connect L and N if two wires are connected).
Connection of RS-232C communication cable
Connect RS-232C communication cable to RS232 connection (TX, RX, GND) of <Figure 4>.
<Figure 5> shows the appearance of OVAL BC2000 controller.
![]() |
<Figure 5> Appearance of OVAL BC2000 controller |